READ AND SAVE THESE INSTRUCTIONSVAPORMIST andVAPORMIST DIELECTRIC STEAM HUMIDIFIERSFor Ducted or Ductless ApplicationsInstallation InstructionsandMai
10START-UP AND OPERATIONIntroductionAfter the system has been properly installed and con-nected to both electrical and water supplies, it may thenbe s
11START-UP AND OPERATIONImportant: Minimum water supply pressure is 10 psi.VAPORMIST DIMake-up Water PipingIn this unit the electronic probe control i
12MAINTENANCEVAPORMIST®Mineral PrecipitateAs evaporation takes place in a standard VAPORMISTunit, the minerals dissolved in the water come out ofsolut
13MAINTENANCE6. Remove the evaporating chamber as follows:Disconnect the flexible connector tube on top of theevaporating chamber, the flexible overfl
14CONTROL PANEL LIGHTS PROBLEM FILL READY DRAIN POSSIBLE CAUSE RECOMMENDED ACTION WATERHumidifier
15VAPORMIST® DI TROUBLE-SHOOTING GUIDE PROBLEMHumidifier willnot heatHumidifier willnot fillWater floatvalve does notcloseReduced or nooutput eventhou
16VM-IOM-1996 Scan.pdf 16 11/19/2009 9:57:23 AM
17REPLACEMENT PARTSNo. Description Qty. Part No.1 Tank 1 160012*2 Cover 1 *3 Thermo Cut-Out 1 409560-0014 Cover, Heater Terminal 1 160750*5 Gasket, Co
18VM-IOM-1996 Scan.pdf 18 11/19/2009 9:57:23 AM
19REPLACEMENT PARTSTable 19-1: VAPORMIST DI (see drawing on page 18)No. Description Qty. Part No.1 Tank 1 160012*2 Cover 1 *3 Thermo Cut-Out 1 409560
2TABLE OF CONTENTSTO THE PURCHASER AND INSTALLERThank you for purchasing our VAPORMIST® humidifier. We have designed and built this equipment to give
20REPLACEMENT PARTSOM-213Table 20-3: SDU SubpanelNo. Description Qty. Part No.1 Relay, 2-Pole 24V 1† 407900-0012 Time delay 24V 1†† 408440-0013 Fuse
21 DATEINSPECTED PERSONNEL OBSERVATION ACTION PERFORMEDMAINTENANCE SERVICE RECORDVM-IOM-1996 Scan.pdf 21 11
22TWO-YEAR LIMITED WARRANTYDRI-STEEM Humidifier Company (“DRI-STEEM”) warrants to the original user that its products will be freefrom defects in mate
3Figure 3-2: VAPORMIST DI Humidifier(Deionized Water)The VAPORMIST DI humidifiershown here is specifically designedfor use with deionized or reverseo
4INSTALLATIONFigure 4-2: Mounted Horizontally in Duct and LowerThan VAPORMIST UnitLocating and Mounting the VAPORMIST®HumidifierThe VAPORMIST humidif
5INSTALLATIONVAPORMIST® Mounting Tubewith Condensate Drain Line• Mount dispersion tube level.• For best vapor absorption, orientdispersion tube so t
6PIPING AND WIRINGFigure 6-1: Drain Adjacent to WallDrain Piping ConfigurationsFigure 6-2: Drain Through or in WallHumidifier CabinetAppropriate red
7ELECTRICAL SPECIFICATIONS AND CAPACITIES/DIMENSIONSBack ViewVapor Hose Opening10.00016.0005.62524.0001½" or 2" Vapor HoseConnection24.000Wa
8AREA-TYPE APPLICATION USING SPACE DISTRIBUTION UNIT (SDU)The SDU converts a VAPORMIST® duct humidifier intoan area-type humidifier. Instead of the s
950% RH 60% RHHumidifierSizeRise(ft.)*Carry(ft.)*Rise(ft.)*Carry(ft.)*VM4 1.0 3.0 1.0 3.5VM6 1.0 3.5 1.5 3.5VM8 1.5 5.0 2.0 5.0VM10 1.5 6.0 2.0 6.0VM1