DriSteem Vaporstream Specifiche Pagina 61

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 80
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 60
57
VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Table 58-1 lists the Area-type steam minimum rise, spread, and throw
nonwetting dimensions. Surfaces or objects located within this minimum
dimension can cause condensation and dripping.
The greater the space relative humidity, the higher and farther the discharged
steam will carry and rise in the space until becoming absorbed.
The Area-type fan and brackets are shipped separately and field-installed on
the humidifier. After mounting the fan, terminate the wires as specified on the
wiring diagram.
To provide power to the Area-type fan, run a neutral line with 208V/240V/
single-phase and 208V/three-phase power supply lines to provide a 120V
circuit for the fan. With all other power supply voltages (other than 120V),
provide a separate 120V circuit for the fan, or order from DriSteem a
transformer installed in the control cabinet.
Area-type fan
INSTALLATION
Dispersion:
Vedere la pagina 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 ... 79 80

Commenti su questo manuale

Nessun commento